Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

AKD Benutzerhandbuch | 25.2.3 AIN.DEADBANDMODE

25.2.3 AIN.DEADBANDMODE

General Information
Type
Description
Units
Range
Default
Value
Data Type
See Also
Start Version M_01-03-06-000
Variants Supported
AKD BASIC
AKD SynqNet
AKD EtherNet/IP
Fieldbus Information
Fieldbus Index/Subindex Is 64 bit? Attributes Signed?
Modbus 1186
Description
When AIN.DEADBANDMODE is set to 0, and the value of the analog input is less than the value of
AIN.DEADBAND, the analog command will be 0. When the analog input is greater or equal to the
AIN.DEADBAND, then the analog command will be generated using the scaling specified.
When AIN.DEADBANDMODE is set to 1, the analog command is 0 if the input is less than the deadband
value. When the input is greater than the deadband, the output is equal to (Input - Deadband) * Scaling.
Below are illustrations of this behavior.
Ain.Deadbandmode = 0 | Ain.Deadband = 1V
-4
-5
NV Parameter
Sets the analog input deadband
mode.
N/A
0 to 1
0
Integer
AIN.DEADBAND (s: 389)
Variant
No
5
4
3
2
1
0
-2
-3
-1
-1
-2
-3
-4
-5
Input
Supported
16 bit
No
1
2
3
4
5
KOLLMORGEN | Mai 2013