Outputs
Potential-free as changeover contacts. Default settings for messages:
Make-up fault
Below minimum pressure
Above maximum pressure
Manual or Stop operation

Note!
For the default settings of the I/O modules,  5.2.3 "I/O module
default settings",  36
All digital inputs and outputs can be set freely as option. Settings to
be made by Reflex Customer Service,  13.1 "Reflex Customer
Service",  56
5.1
Technical data
Housing
Width (W):
Height (H):
Depth (D):
Weight:
Permissible operating temperature:
Permissible storage temperature:
Degree of protection IP:
Power supply:
Fuse (primary):
Inputs, outputs
6 floating relay outputs (changeover)
3 digital inputs 230 V AC
3 digital inputs 24 V AC
2 Analogue outputs (these are not required, because they are already
contained in the Control Touch controller).
Interfaces to the controller
RS-485
19.2 kbit/s
Floating
connection with plug or screw terminals
RSI-specific protocol
5.2
Settings
GEFAHR
Danger to life from electric shock!
Risk of serious injury or death due to electric shock. Some parts of the main
board may still carry 230 V voltage even with the device physically isolated
from the 230 V power supply.
Before you remove the covers, completely isolate the device controller
from the power supply.
Verify that the main circuit board is voltage-free.
5.2.1
Terminator settings in RS-485 networks
Examples for the activation and deactivation of terminators in RS–485 networks.
DIP switches 1 and 2 are located on the main board of the controller.
Maximum length for an RS–485 connection is 1000 metres
Plastic housing
340 mm
233.6 mm
77 mm
2.0 kg
-5 °C – 55 °C
-40 °C – 70 °C
IP 64
230 V AC, 50 – 60 Hz (IEC 38)
0.16 A time-lag
Variomat Touch — 22.07.2024
I/O module (optional expansion module)
Device controller with I/O module
1
Relay outputs of the I/O
module*
6 digital outputs
2
I/O module
Connections of the I/ O
3
conductors
* The 2 analogue outputs are not required because the Control Touch controller
already has two analogue outputs for pressure and level measurement.
Terminator settings
Jumper/switch
Settings
Jumper J10
Activated
and J11
Deactivated
DIP switch 1
Activated
and 2
Deactivated
Device controllers and I/O module in Master-Slave function
1
Control Touch controller in
Master function
2
I/O module for the Master
function
3
Control Touch controller in
Slave function
Master function
Terminator settings
Jumper/switch
Settings
Jumper J10
Activated
and J11
Deactivated
DIP switch 1
Activated
and 2
Deactivated
Slave function
Terminator settings
Jumper /
Settings
Switch
Jumper J10
Activated
and J11
Deactivated
DIP switch 1
Activated
and 2
Deactivated
4
"Control Touch" controller
5
RS-485 connection
6
Optional RS-485 connection
Master - Slave
Field bus
I/O module
Control Touch
X
---
---
---
---
X
---
---
4
I/O module for the Slave
function
5
I/O module for expansion
I/O module
Control Touch
X
---
---
---
---
---
---
I/O module
I/O module
Control Touch
for expansion
---
X
X
---
---
---
---
---
English — 35