Controller
A three-digit PM code is assigned to the setting options
PM Code Description
001
Select the language
002
Set the time
003
Set the date
Execute null balancing
–
The primary vessel must be empty
–
The system checks whether the signal from the level sensor
matches the selected primary vessel.
005
Set the minimum operating pressure P
switching points", 40.
Degassing >
010
•
Degassing programme
–
No degassing
–
Continuous degassing
–
Interval degassing
–
Run-on degassing
011
•
Continuous degassing time
Make-up >
023
•
Maximum make-up time ...min
024
•
Maximum make-up cycles ... /2 h
027
•
With water meter "Yes/'No"
–
If "Yes", continue with 028
–
If "No", continue with 007
028
•
Make-up quantity (Reset) "Yes/No"
–
If "Yes", reset to "0"
029
•
Maximum make-up quantity ... l
030
•
Softening "Yes/'No"
–
If "Yes", continue with 031
–
If "No", continue with 007
007
Maintenance interval... months
008
Floating contact
•
Message selection >
–
Message selection: only messages marked with "√" are
output.
–
All messages: All messages are output.
015
Change remote data "Yes/No"
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
009
•
Brightness ... %
010
•
Screen saver brightness ... %
011
•
Screen saver delay ...min
018
•
Secure access "Yes/No"
Information >
•
Vessel
•
Volume
•
Weight
•
Diameter
•
Position
–
Position in %
•
Software version
10.3.1.2 Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
44 — English
, 8.2 "Variomat
0
Variomat 140 — 25.09.2020 - Rev. A
1.
Press "Settings".
–
The controller switches to the setting area.
2.
Press "Customer >".
–
The controller opens the Customer menu.
3.
Press the required area.
–
The controller switches to the selected area.
–
Use the scroll bar to navigate through the list.
4.
Set the system-specific values for the individual areas.
•
Use the "Left" and "Right" buttons to select the display value.
•
Use the "Up" and "Down" buttons to change the display value.
•
Confirm your entries with "OK".
–
Press "i" to display a help text for the selected area.
–
Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
10.3.2
Service menu
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service.
10.3.3
Default settings
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Language
DE
Minimum operating
1.8 bar
pressure "P
"
0
Next maintenance
12 months
Volt-free contact
All
Make-up
Maximum make-up
0 Litres
quantity
Maximum make-up time 20 minutes
Maximum make-up
3 cycles within
cycles
2 hours
Comment
Display language.
8.2 "Variomat switching
points", 40.
Time left to the next due
maintenance.
Only if make-up has been
selected in the customer menu
with "With water meter Yes".