I/O module (optional expansion module)
5.2.3
I/O module default settings
The inputs and outputs of the I/O module each have default settings.
These default settings can be changed, if required, and adjusted to local
conditions.
Responses by the inputs 1 – 6 of the I/O module are recorded and displayed in
the device controller's fault memory.
Location
Signal evaluation
INPUTS
1
N.C.
2
N.C.
3
N.C.
4
N.O.
5
N.O.
6
N.O.
OUTPUTS
1
Changeover contact
2
Changeover contact
3
Changeover contact
4
Changeover contact
5
Changeover contact
6
Changeover contact
5.3
Replacing the fuses
DANGER
Risk of electric shock!
Risk of serious injury or death due to electric shock. Some parts of the main
board may still carry 230 V voltage even with the device physically isolated
from the 230 V power supply.
Before you remove the covers, completely isolate the device controller
from the power supply.
Verify that the main circuit board is voltage-free.
Fusing is provided on the I/O module's main circuit board.
32 — English
Fault memory
Message text
entry
External temperature
Yes
monitoring
External signal,
Yes
Minimum pressure
Manual make-up
Yes
Emergency-Off
Yes
Manual pump 1
Yes
Manual OF-1
Yes
---
---
---
---
---
---
---
---
---
---
Make-up fault
---
Variomat 140 — 25.09.2020 - Rev. A

Note!
Default settings apply to software version V1.10 and higher.
All digital inputs and outputs can be set freely as option. The
setting is carried out by Reflex Customer Service,  13.1 "Reflex
Customer Service",  49
Priority
Signal on the input triggers the following action
Yes
Solenoid valves are closed.
Solenoid valve (2) in overflow line (1)
Solenoid valve (3) in overflow line (2)
Output relay (1) is switched.
No
Solenoid valves are closed.
Solenoid valve (2) in overflow line (1)
Solenoid valve (3) in overflow line (2)
Output relay (2) is switched.
Yes
Solenoid valve (1) in make-up line is manually opened.
Output relay (5) is switched.
Yes
Pumps (1) and (2) are switched off.
Solenoid valves (2) and (3) in the overflow lines are closed.
Solenoid valve (1) in the make-up line is closed.
Switches "Group alarm" in the device controller.
Yes
Pump (1) is manually switched on.
Output relay (5) is switched.
Yes
Solenoid valve (1) is opened.
---
See input 1
---
See input 2
---
Below minimum pressure.
"ER 01" message in the controller
---
Maximum pressure exceeded
"ER 10" message in the controller
---
Switches in manual mode
Switches in stop mode
Switches with inputs 3,5,6 active
---
Make-up setting values exceeded.
Switches the following messages in the device controller:
"ER 06", Make-up time
"ER 07", Make-up cycles
"ER 11", Make-up quantity
"ER 15", Make-up valve
"ER 20", Maximum make-up quantity
1
Microfuse F1 (250 V, 0, 16 A slow)
Proceed as follows:
1.
Disconnect the I/O module from the power supply.
Pull the power plug from the bus module.
2.
Open the terminal space cover.