Operation
Indication on the
Meaning
display
Cancel
Select "Yes" or "No" on the controller display and confirm
calibration?
with "OK" on the controller control panel.
No
Yes: The "RG" primary vessel is fully emptied and the
device is installed as per the instructions.
Calibration is still not possible, confirm with
"Yes". The start routine is terminated. Use the
customer menu to repeat the calibration,  9.2
"Configuring settings in the controller",  31.
Contact Reflex Customer Service,  12.1
"Reflex Customer Service",  37.
No: The start routine restarts.
Check the prerequisites for the commissioning,
 7.1 "Checking the requirements for
commissioning",  29.
Terminate start
This message appears on the display only after calibration
routine?
has been successful.
No
Select "Yes" or "No" on the controller display and confirm
with "OK" on the controller control panel.
Yes: The start routine is terminated, the device
automatically switches to Stop mode.
No: The start routine restarts.
0 % / 2.0 bar
The level indication is at 0 %.
STOP

Note!
After successful conclusion of the start routine, you are in Stop mode. Do
not yet switch to Automatic mode.
7.4
Venting the vessel
CAUTION
Risk of burns on hot surfaces
Excessive surface temperatures on the compressor can result in skin burns.
Wear suitable personal protective equipment (safety gloves, for
example).
Upon completion of the start routine, the primary vessel must be vented.
Open the vessel's discharge ports to allow the air to escape.
Select Automatic mode on the controller's operator panel,  8.1.1
"Automatic mode",  30.
The "CO" compressor builds up the pressure required venting. This pressure is
0.4 bar above the set minimum operating pressure. The vessel's diaphragm is
acted on by this pressure and the water side in the vessel is vented. Close the
discharge ports of all vessel after the compressor has been automatically shut
down.

Note!
Inspect all compressed air connections between the control unit and the
vessel for leaks. Subsequently, slowly open all cap valves at the vessel to
create the water-side connection to the system circuit.
7.5
Filling the vessel with water
Prerequisite for fault-free filling is a make-up pressure at least 1.3 bar above the
set minimum pressure "P
".
0
Without automatic make-up:
Use the discharge ports or the system circuit to manually fill the vessel
to approximately 30 % of the vessel volume,  6.4 "Make-up and
degassing variants",  27.
With automatic make-up:
The vessel is automatically filled to approximately 12 % of the vessel
volume,  6.4 "Make-up and degassing variants",  27.
7.6
Starting Automatic mode
Automatic operation can be set after initial commissioning. Start the automatic
mode at the operator panel of the controller.
The following prerequisites must be met for automatic operation:
The device is filled with compressed air and water.
All required parameters are defined in the controller.
30 — English
Press "Auto" for automatic mode at the controller operator panel.
The "Auto" LED at the operator panel illuminates to visually signal automatic
mode.

Note!
Initial commissioning is completed and the device is in continuous
operation.
8
Operation
8.1
Operating modes
8.1.1
Automatic mode
Use:
After initial commissioning has been successfully completed
Start:
Press "AUTO".
Functions:
Automatic mode is suitable for continuous device operation and the controller
monitors the following functions:
The "CO" compressor and the "PV1" solenoid valve are regulated by the
controller so that the pressure remains constant in a regulation range of ±
0.1 bar.
Faults are indicated and evaluated in the display.
8.1.2
Manual mode
Use:
For testing and maintenance tasks.
Start:
Press "Manual" on the controller. The Auto LED at the operator panel flashes to
visually indicate that Manual mode is active.
Functions:
Manual mode allows you to select the following functions and to perform a test run:
"CO" compressor.
"PV1" overflow solenoid valve.
The solenoid valve of the "WV1" make-up.
You can switch several functions after each other and test them at the same time.
30 % 2.5 bar
CO1!* PV1 WV1
Press "OK".
"Quit" button
"Auto" button

Note!
Manual operations cannot be performed if safety-relevant parameters
would be exceeded. Switching is then disabled.
Reflexomat Silent Compact — 06.12.2023
Pressurisation
Expansion volume compensation
Automatic make-up.
Use the "Switch up/down" keys to select the function.
"CO1" = compressor
"PV1" = Solenoid valve in the overflow line
"WV1" = solenoid valve make-up
(* selected and active units are marked with "!").
Confirm the selection or shut-down of the individual functions.
Shut-down of the individual functions in reverse order.
Press "Quit" for the last time and the system moves in Stop mode.
Return to Automatic mode.