AVENTICS | DeviceNet | R499050019–BDL–001–AD
O
Assign the station address from 0 to 63 using S1 and S2. The
maximum MAC ID is 63!
– S1: Tens digit from 0 to 9
– S2: Unit digit from 0 to 9
– S1 + S2 = station address
Default: MAC ID = 1
Do not use address 0, it causes a system stop.
7.1.3

Setting the diagnostic messages

The S3 mode switch used to set the diagnostic messages is
located under the PG fitting A (see Fig. 8 on page 106).
When delivered, the diagnosis is deactivated (S3/5 set to OFF).
O
Activate or deactivate the diagnostic message to the master
with the S3.5 switch.
The modified switch position will only be activated after a
new "power on".
This setting can also be assigned using the Module Control
Object. If assigned via the Module Control Object, the position
of S3.5 will become ineffective.
7.1.4

Assigning the valve supply

The S4-S6 switches for assigning the valve supply are located
beneath the PG screw cap B (see Fig. 9). The following is
assigned to each switch:
W
4 subbase positions for double solenoid valves
(with solenoids 12 and 14) or
W
8 subbase positions for single solenoid valves
(with solenoid 14).
Commissioning and Operation
107