AVENTICS | DeviceNet | R499050019–BDL–001–AD
13.4.4
Module Control Register (MCR)
The behavior of the bus coupler can be changed with the 16-bit
wide Module Control Register.
The default value of the register (after power-on) depends on
the position of the S3.5 DIP switch 5 (see "Assigning the valve
supply" on page 107):
– S3.5 = OFF default value: 0x0000
– S3.5 = ON default value: 0x0002
Table 45:
Module Control Register class 0x66 inst. 0x01 attr. 0x64
MSB
Bit
Bit
Bit
15...6
5
4
0
0
0
1
1
X
0
0
LSB
Bit
Bit
Bit
Bit
3
2
1
0
0
1
0
1
0
0
0
1
1
X
143
Appendix
Default
configuration of the
diagnostics
Keep current
configuration
Activate the default
configuration
Diagnostic Data
(see below)
Do not map in the
assembly object
Map behind the
input data in the
assembly object
Behavior with run
-> idle
All outputs = "0"
Last state
Reserved
Behavior with run
-> fault
All outputs = "0"
Last state
Reserved
Reserved