8.6.12 Setpoint ramp (4.1.9)
Setpoint ramp
Description
When the function is enabled, setpoint changes are affected by the
setpoint ramp, and the setpoint changes gradually over a period of
time.
Proportional pressure or Setpoint influence are not affected by
this function.
If the multisensor function is enabled, it will have a higher
priority than the setpoint ramp which will be overruled.
Setting range
The function can be enabled and Change per minute can be set.
Setting via the operating panel
•
Settings > Primary controller > Setpoint ramp.
1. Select: Enabled.
2. Set: Change per minute.
Factory settings
The function is disabled.
38
8.6.13 Pump cascade control (4.2)
Pump cascade control
In the menu, you can set the functions connected to pump cascade
control.
The following menus can be selected:
•
Min. time between start/stop
•
Max. number of starts/hour
•
Standby pumps
•
Forced pump changeover
•
Pump test run
•
Pilot pump
•
Pump stop attempt
•
Pump start and stop speed
•
Min. performance
•
Compensation for pump start-up time.