8.7.42 Remote sensors (4.3.25)
Fig. 96 Remote sensors
Description
The function allows you to enter the phone number for CU 354.
The number must start with the country code (e.g. +45 for
Denmark). All remote sensors must send their data batch to this
phone number.
Enter the number of remote sensors in the water distribution
network. The display shows the status of each remote sensor.
Setting range
•
Local phone number for the CIU 250 box connected to the
controller.
•
Number of remote sensors.
Setting via operating panel
•
Settings > Secondary functions > Remote sensors
1. Enter the local phone number.
2. Enter the number of sensors.
3. Select one of the remote sensors.
Factory setting
Number of sensors: 1
48
8.7.43 Remote sensor 1-10 (4.3.25.1)
Fig. 97 Sofrel logger
Description
The function allows you to enable the remote sensor and select
the installed sensor type. It is also possible to rename the sensor
for easy identification, for instance by using the street name or zip
code.
You can enter a setpoint for the sensor. Based on the logged
data, CU 354 controls the outlet pressure at the pumping station
to achieve the set pressure at the remote sensor.
The sensor can be set to give an alarm if the pressure falls below
the defined minimum pressure.
You can see when the latest response from the remote sensor
was received. The remote sensor will send the logged data once
every 24 h (normally during the night).
Setting range Sofrel logger
•
Setting the remote sensor to enabled.
– Select the sensor type
•
Entering a unique name for the remote sensor.
•
Entering the remote sensors phone number.
•
Setting the setpoint.
•
Set warning reset
Setting via operating panel
•
Settings > Secondary functions > Remote sensors> Remote
sensors 1-10
1. Select: Enabled.
2. Select Sofrel LS42
3. Enter a unique name for the remote sensor.
4. Enter the phone number of the remote sensor.
5. Set the setpoint, that is the minimum pressure at the critical
point.
6. Set warning reset to manual or auto
7. Press: Back
8. Set the next sensor.
Factory setting
Disabled.
Setpoint: 1.8 bar.