8.7.30 Analog inputs and measured value (4.3.8.1.1 -
4.3.8.7.1)
Fig. 81 Analog inputs and measured value
Description
A function can be related to the individual analog inputs.
Setting range
You can select one function per analog input. For further details,
see section
9. Measuring
parameters.
•
Not used
•
0-100 % signal
•
Inlet pressure
•
Discharge pressure
•
External pressure
•
Flow rate-3
•
Tank level, suction side
•
Water temperature
•
Ambient temperature
•
Power, pump 1-6
Setting via operating panel
•
Settings > Secondary functions > Analog inputs.
1. Select "Analog inputs".
•
Select "Measured input value" and display 4.3.8.1.1 appears.
2. Select input.
3. Press [Back].
4. Set the minimum and maximum sensor value.
8.7.31 Digital outputs (4.3.9)
Fig. 82 Digital outputs
Description
Each digital output can be activated and related to a certain
function.
As standard, the system has nine digital outputs.
All digital outputs are shown so that their physical position in the
system can be identified.
Example
DO1 (IO 351-41) [71]:
DO1
Digital output No 1
(IO 351-41)
IO 351B, GENIbus number 41
[71]
Terminal No 71
For further information on the connection of various digital
outputs, see the wiring diagram supplied with CU 354.
8.7.32 Function of digital outputs (4.3.9.1 - 4.3.9.16)
Fig. 83 Function of digital outputs
Description
A function can be related to the individual outputs.
43