Operation via Ethernet/OPC UA

Access via Ethernet (independently of the web browser) is available
as from firmware version 1.2. OPC UA is only available from hard-
ware version 2.0 and firmware versions 1.4 and later.
You can simultaneously make two connections to the ClipX's web
server, one TCP/IP connection and two OPC UA connections.
You can also operate the ClipX with no fieldbus, or in addition to the fieldbus via
the Ethernet port on X1. When operating simultaneously via fieldbus and Ether-
net, you must make sure you do not access the same settings simultaneously,
as the same resources (buffer memory etc.) are used internally for all variants.
The behavior of the ClipX will otherwise not be defined, and might result in mal-
functions and corrupted data.
You can also send data (over two channels) to the ClipX. The data is then dis-
played in the browser, and can also be polled over the fieldbuses.
8.1

Accessing via standard Ethernet and object dictionary

You can also send the commands and functions provided via the Ethernet port
at X1 to the ClipX. The ClipX only supports one client at a time via Ethernet;
multiple connections are not possible. The connection to the web server in the
ClipX can also be made through a browser (Firefox, Edge, Chrome, etc.), and is
independent of this Ethernet connection – see also
web browser" on page
Important: Access cannot be protected by password or https. Make
sure that no unauthorised access is possible over the network.
ClipX
84.
A04643_04_X00_03 HBM: public
Operation via Ethernet/OPC UA
"Setting the ClipX using a
109