Operation via fieldbus
You can download a default PROFIBUS GSD file via your web browser's
Device Storage menu or from the HBM website: https://www.hbm.com/ClipX.
DPV0 (Cyclical data content)
During the cyclic transmission of measured or calculated values, 5 bytes are
transmitted on PROFIBUS (and only here): 4 bytes for the measured value
(FLOAT) and 1 byte (USINT) for the status of this value. This applies to the fol-
lowing measured values: Electrical value (Field value), Gross, Net, Minimum
value, Maximum value, Peak-to-Peak, Captured value 1/2, ClipX bus value 1 ...
6, Calculated value 1 ... 6, External Eth. value 1/2 and Analog Output. If the sta-
tus byte equals 0, the respective value is valid; if the status byte is not equal to
0, the value is invalid.
The External FB value 1/2 is the exception, it is only transmitted with 4 bytes
(without status).
See also
"Data transfer from the ClipX to the controller" on page
129.
DPV1 (Acyclic data content)
The DPV1 objects are addressed by way of Slot and Index. Whether a module
has been configured in a ClipX PROFIBUS slot (and if so, which one) is irrele-
vant. There are, however, PROFIBUS configuration tools that only send DPV1
requests when there is actually a module in the scanned slot. In this case you
must fill up the empty slots.
CiA404-compliant objects are located in slot 4.
DPV1 objects
R/W (access mode): RO = read only, RW = read and write, WO = write only.
UINT = unsigned integer.
Index and Subindex of the ClipX object directory are given for information only.
ClipX
135
A04643_04_X00_03 HBM: public