Starting up the ClipX
threshold and above in the case of Below threshold. In Above or below
threshold mode the hysteresis is both above and below (example 2).
If the source signal is invalid, no pulse is generated. The values for limit value
and hysteresis are not checked.
Example 1: Above threshold mode
Signal at Input
1
0
Fig. 41: Trigger condition is Above threshold
Example 2: Above or below threshold mode
Signal at Input
1
0
Fig. 42: Trigger condition is Above or below threshold
7.4.2.5
Automatic mean
The calculation filters an easily usable signal from a severely fluctuating or noisy
signal by using a specific segment of the signal curve to compute a mean value.
This enables you to reduce the impact of overlaid interference. You can also
92
A04643_04_X00_03 HBM: public
Threshold
Hysteresis
Trigger Flag
t
Hysteresis
Threshold
Hysteresis
Trigger Flag
t