Operation via fieldbus
Subin-
Index
dex
0x4428
8
0x4428
9
0x4428
20
0x4428
21 ... 26
0x4428
27
182
Function
Number of values per sec-
ond (recording rate) that are
to be stored during continu-
ous filling or checked for
conditions (digital flags or
difference values).
Time of recording the first
value in the FIFO according
to the ClipX date/time.
Command: Read a FIFO
entry from all 6 FIFO chan-
nels and buffer it for subse-
quent reading (subindex 21
... 27). The entry is deleted
after this command.
Buffered measured value
from the FIFO channels 1 ...
6.
Buffered time from the
FIFO.
A04643_04_X00_03 HBM: public
Value
0.1 ... 1000.0, FLOAT.
Date and time, e.g. "17.08.18
14:00:37", STRING, RO.
If there are no values in the
FIFO, subindex 21 ... 27 is used
for the measured values 1.001
30
* 10
and 0xffffffff for the time;
RO.
FLOAT (Byte order Little
Endian), RO.
An invalid measurement value
is always replaced by 1.001 *
30
10
; any defined substitute
value is not used.
Time in ms since saving the first
value, UINT32, RO.