Electrical connections, LEDs
6.9

Connecting the analog output

You can output voltage (±10 V) or current (4 ... 20 mA). The analog output is
short-circuit-proof, the bandwidth is 3.8 kHz, the update rate is 19.2 kHz.
See also
"Available connections and LEDs" on page
Fig. 26: Plug terminal X3, pin assignment for analog output

Start-up behavior

On starting up the ClipX (power on), the analog output initially has a high output
resistance. After initializing, the status of the settings is determined in the Start
parameter set.
The factory default setting is: Output deactivated, gross signal as input (source),
zero value 0 V, scaling 0/0 and 5/5, value in case of "invalid" signal 0 V and test
signal 0 V (both inactive).
Value in case of error
Which value is outputted depends on whether you activate the value in case of
an "invalid" signal or not. Make the setting via the ClipX web server in your
browser.
1. Value in case of "invalid" signal active (switch in browser on the right and
red)
If the input signal becomes invalid, or the output signal would be outside the
range of ±11 V or less than 3 mA or greater than 21 mA, the specified value
is outputted.
2. Value in case of "invalid" signal not active (switch in browser on the left and
gray)
The highest or lowest possible value is outputted depending on the signal
(±11 V, or 3 mA or 21 mA).