Herunterladen Inhalt Inhalt Diese Seite drucken

HBM ClipX Bedienungsanleitung Seite 187

Vorschau ausblenden Andere Handbücher für ClipX:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Subin-
Index
dex
0x4400
1
3
1)
DC = direct voltage; CF = carrier frequency
Filter
Subin-
Index
dex
0x4401
1
2
ClipX
Function
Define sensor type.
Unit for Pt100.
Function
Characteristic
Cut-off frequency (-3 dB)
A04643_04_X00_03 HBM: public
Operation via fieldbus
Value
0: Volt ±10 V
1: Current 4 ... 20 mA
2: Current ±20mA
3: Pt100
4: Potentiometer
5: Full bridge 5 mV/V (DC
6: Full bridge 2.5 mV/V (DC)
7: Full bridge 5 mV/V (CF
8: Full bridge 2.5 mV/V (CF)
9: Half bridge 5 mV/V (DC)
10: Half bridge 2.5 mV/V (DC)
11: Half bridge 5 mV/V (CF)
12: Half bridge 2.5 mV/V (CF)
13: Full bridge 100 mV/V (DC)
14: Full bridge 800 mV/V (DC),
UINT8.
0: °C
1: K
2: °F, UINT8.
Value
1: Filter off
2: Butterworth
3: Bessel, UINT8.
0.02 ... 3000.0 Hz, FLOAT.
1)
)
1)
)