Herunterladen Inhalt Inhalt Diese Seite drucken

Shielding And Grounding Design - HBM ClipX Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für ClipX:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Electrical connections, LEDs
6.2

Shielding and grounding design

The supply voltage connection, as well as the signal and sense leads, must be
installed in such a way that electromagnetic interference does not adversely
affect module functionality (HBM recommendation: "Greenline shielding design"
– see http://www.hbm.com/Greenline). Always connect the cable shield by the
shortest possible length to the plug terminals and, as far as possible, lay the
shield flat at the control cabinet inlet with shield connection clamps, e.g. type
SKS 8-SNS35 – 3062786 from Phoenix Contact – see illustration of shield
clamp.
Fig. 7:
Shield clamp for flat contacting of cable shields (example)
Double-shielded connecting cables, e.g. for sensors
We recommend using HBM cable Kab 7.5/00-2/2/2 wherever possible. The
cable is double-shielded and low in capacitance. When using double-shielded
cables, connect the outer shield only to the connection for the housing (ground
symbol
, labeled "Outer cable shield" in the connection diagrams), not to one
of the GND connections (
). In the case of control cabinets, also lay this shield
S
contacting on the cabinet – see illustration of shield clamp. Connect the inner
shields of the sensor cables to the connection labeled "Inner cable shield" (
).
S
Use the shortest lines possible for the connections.
Applications in areas with potentially explosive atmospheres are exceptions.
There connect all cable shields to the potential equalization connection.
Single-shielded cables
Connect the shields of single-shielded cables to the connection for the housing
(ground symbol
, labeled "Outer cable shield" or "Cable shield" in the connec-
tion diagrams), not to one of the GND connections (
). In the case of control
S
cabinets, also lay this shield contacting on the cabinet – see illustration of shield
clamp.
ClipX
23
A04643_04_X00_03 HBM: public

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis