CHLORIDE 70-NET 10 - 40KVA
Output
UPS output
Nominal voltage
Voltage tolerances
Nominal frequency
Frequency tolerance
Frequency change rate
Permissible non-linear load
according to EN 50 091-1
Overload capability (3-
phase)
Nominal apparent power
Nominal active power
Nominal current
Heat
UPS Battery
a)
Heat emission
Airflow rate
Electronic bypass:
Max. overload current
for 10ms, with selective
external bypass fuse F1
a) Conversion power loss in BTU[h] = P
Notice
Consider the information given on the back of the device.
User Handbook - 10H52163PAMC rev.9 - 06/2008
Rating [kVA]
UPS 10k
static
dynamic
[Hz]
self-clocked
line-clocked
[Hz/s]
up to 5 min
up to 30 s
at [kVA]
cos ϕ
= 0.8
ind
[kW]
at 400 V,
cos ϕ = 0.8 [A]
Rating [kVA]
[kW]
at 100% load
at 75% load
at 50% load
idle
3
[m
/h]
[A]
[kW] *3412
V
UPS 15k
UPS 20k
3 AC/N 400 V, 380 V or 415 V parameterisable
+ 1 % with symmetrical load
+ 3 % with 50 % unbalanced load
+ 4 % with 100 % unbalanced load (single-phase)
IEC/EN 62040 - 3 ch.1 (VFI, SS, 111)
50 or 60 + 10 %
+ 0.1 %
+ 1 % (adjustable to + 2 % , + 3 % or + 4 %)
0.1 (adjustable to 1 or 2)
100 %
1.25 x I
1.5 x I
10
15
8
12
14
22
10
15
0.7
1.0
0.6
0.8
0.5
0.6
0.3
0.3
500
500
200
350
TECHNICAL DATA
UPS 30k
UPS 40k
nom
nom
20
30
40
16
24
32
29
44
58
20
30
1.4
2.1
2.8
1.0
1.6
2.1
0.7
1.2
1.6
0.3
0.5
0.6
500
500
500
600
800
800
Page 55
ENG