Important: On the first device you must enable Sync Mode Master [Master
sync mode]. All the others operate as slaves, so the switch must not be
active. Make the setting in your browser using the Amplifier and Sensor
Type menu items. Synchronization is only possible for sensor types with
carrier frequency (CF), not for DC. No synchronization of the time base or the
A/D converters takes place.
CxA
CxB
Sync
DI2
DI1
DO2
DO1
0V
24V
Abb. 35: Plug terminal X2, pin assignment for Sync signal
Important: Termination resistors are not necessary, and must not be used.
The maximum cable length between two devices is 30 cm.
58
Housing, cable shields
ClipX bus
X
ClipX bus GND
ClipX bus
Synchronization
DI
Digital In GND
Digital In 2
Digital In 1
Digital Out 2
Digital Out 1
Supply 0 V
Supply 10 ... 30 V
CxA
X
CxB
Sync
DI
DI2
DI1
DO2
DO1
0V
24V
Electrical connections, LEDs