Byte, see above) you must also specify a parameter here, e.g. 0. The Zero command is
SDO 0x4410,4,0LF
thus
Write request from the controller to the ClipX (Object Dictionary Write Request)
Field name
Index
UINT
Subindex
USINT
Padding
USINT
Byte
Value
UDINT
or REAL
(FLOAT)
This will avoid unintentional writing
Use the following sequence:
1.
Set index 0x0000 (no operation).
2.
Set Subindex and Value.
3.
Set desired index.
The ClipX only evaluates the request after the third step.
Response from the ClipX to the write request (Object Dictionary Write Response)
The value was successfully written if Index and Subindex match the request and no
error bit is set.
Field name
Index
UINT
Subindex
USINT
Error Bits
USINT
ClipX
Operation via fieldbus
.
Data
type
Index of object to write.
0x0000 (no operation) sets the response to zero.
Subindex of object to write.
No function.
The value of the object. The data type depends on the
object.
Data
type
Index of the written object.
Subindex of the written object.
0x01: Access error, e.g. write access to read-only object.
0x02: Format error, e.g. unsupported data type.
0x04: Not found, i.e. the object does not exist.
Explanation
Explanation
163