Herunterladen Inhalt Inhalt Diese Seite drucken

HBM ClipX Bedienungsanleitung Seite 217

Vorschau ausblenden Andere Handbücher für ClipX:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Limit switches
Index
Subindex
0x4600
1
0x4601
1 ... 4
0x4602
1
0x4603
1 ... 4
0x4604
1 ... 4
0x4605
1 ... 4
0x4606
1 ... 4
0x4607
1 ... 4
0x4608
1 ... 4
0x4609
1 ... 4
0x460A
1 ... 4
ClipX
Operation via fieldbus
Function
Bit-wise status of all limit
switches.
Status of a single limit
switch.
Clear one or more limit
switches (from hysteresis)
if corresponding bit is set.
Clear a single limit switch.
Limit value.
Value of hysteresis or range
(band mode).
Select signal source.
Mode.
Clear by, bit mask Low word
(32 bit).
Clear by, bit mask High
word (32 bit).
Clear by inverting.
Value
0 ... 15, only lowest 4 bits,
UINT8, RO.
0: Not triggered
1: Triggered, UINT8, RO.
0 ... 15, only lowest 4 bits;
Clear if bit = 1, UINT8, WO.
0: No action
1: Clear, UINT8, WO.
FLOAT.
0 ... 31, see
„List of signal refer-
ences" on page
218, UINT8.
1: Above level
2: Below level
3: In band
4: Outside band, UINT8.
32
0 ... 2
-1, see
„Digital flags:
List of I/O flags (I/O status)" on
page
157. UINT32.
0: Not inverted1: Inverted,
UINT8.
215

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis