Moving average/RMS (block type 22), available with firmware 2.8 or higher
Index
Subindex
0x510n
20
21
22
23
30
FIR filter (block type 23), available with firmware 2.8 or higher
Index
Subindex
0x510n
20
21
30
212
Function
Input.
Filter width.
Arithmetic mean/root mean
square value (true RMS)
Reset Flag.
Output.
Function
Input.
Cut-off frequency (-3 dB).
Output.
Value
0 ... 47, see
„List of signal refer-
ences" on page
218, UINT16.
1 ... 4000, UINT16.
Indication of calculation mode:
0: Arithmetic mean
1: RMS value, UINT8.
Flag number 0 ... 63, see
tal flags: List of I/O flags (I/O
status)" on page
157. UINT8.
21 ... 26, 48, see
„List of signal
references" on page
UINT16.
Value
0 ... 47, see
„List of signal refer-
ences" on page
218, UINT16.
2.0 ... 100 Hz, FLOAT.
21 ... 26, 48, see
„List of signal
references" on page
UINT16.