Verfügbare Sprachen

Analog output
Index
Subindex
0x4500
1
2
3
4
5
6
7
8
9
10
11
14
190
Function
Type
Source
Two-point scaling: 1st
Point source value (physi-
cal).
Two-point scaling: 2nd
Point source value (physi-
cal).
Two-point scaling: 1st
Point electrical (value at
analog output).
Two-point scaling: 2nd
Point electrical (value at
analog output).
Zero value (electrical).
Value in case of "invalid"
signal
Activate value in case of
"invalid" signal.
Test signal (electrical).
Activate test signal.
Validity of two-point scal-
ing.
Value
0: Off
1: Volt ±10 V
2: Current 4 ... 20 mA, UINT8.
0 ... 30, see
„List of signal refer-
ences" on page
218, UINT8.
FLOAT.
0: Not active
1: Active, UINT8.
(Only in case of value "invalid").
FLOAT.
0: Not active
1: Active, UINT8.
0: Valid
1: Invalid, INT8, RO.