Electrical data of digital inputs
Voltage class:
None.
Insulation voltage:
50 V (in relation to earth).
Insulation test voltage:
None.
Output voltage:
12 V.
Input current:
8 mA.
Input filter time (software):
150 ms.
Input filter time (hardware): 20 ms.
The digital inputs are not short-circuit-proof.
Outputs
The controller has up to twelve digital outputs (depending on the
options chosen) which are potential-free changeover contacts.
The signals from the digital outputs can be passed on to a
building management system.
Digital outputs
Designation Digital outputs
DO1
Common fault
DO2
Fault, sensor cable
DO3
Pump running
DO4
Pump running
DO5
Circuit voltage available
DO6
Fault, circuit voltage
DO7
Pump switched off
DO8
Release pressure switches
DO9
Defective DPC 300 V
DO10
Louvres activated (optional)
DO11
Ventilator running (optional)
DO12
Low level in priming tank (optional)
Digital output X3, 13 is for connection of the stop valve.
See section
10.2 Electrical
connection.
Electrical data of signal relay outputs
Voltage class:
Category 1.
Insulation voltage:
115 V (in relation to earth).
Insulation test voltage: 1.5 kVAC.
Max. supply voltage:
115 VAC.
Max. load:
2 A, 115 V.
Min. load
100 mA, 12 VDC.
Max. load power:
230 VA / 24 W.

7.1 Factory settings

See section
8.2 Settings
for information on setting the controller.
Mains monitor B6, flasher relay K13 and impulse relay K14 are
set at the factory. The settings must not be changed.
10

8. Control panel

The control panel is used to set parameters, to display status and
alarm indications via the display and the indicator lights as well as
to reset alarms.
The control panel is divided into two parts (see fig. 4):
the display with operating buttons
the status and fault indicator lights.
The indicator light part is subdivided into these parts:
fault indications, battery A and B
alarm indications
status of fuel tank
status indications.
Terminal
X4, 1-3
X4, 4-6
X4, 7-9
X4, 10-12
X4, 13-15
X4, 16-18
STATUS
X4, 19-21
X4, 22-24
X4, 25-27
X4, 28-30
X4, 31-33
Fig. 4
Control panel
X4, 34-36
Display
The display shows the status via operating data and warning
messages as well as the individual setting displays.
The setting displays are described in section
the warning messages are described in section
indications. Figure
1700 rpm
Press1
T = 40 °C
Oil = 10b
00000H
Fuel = 100 %
B1 = 24 V
B2 = 24 V
Fig. 5
Example of status display
DPC 300 V
BATTERIE A
BATTERIE B
BATTERIE/LADEGERAT STORUNG
BATTERIE/LADEGERAT STORUNG
BATT./BATT.CHARGER FAILURE
BATT./BATT.CHARGER FAILURE
ALARME
STORUNG STEUERGERAT
STORUNG KUHLWASSERHEIZUNG
ALARM COOLING WATER HEATER
DIESEL CONTROLLER FAULT
OLDRUCKMANGEL
STORUNG SENSORKABEL
LOW OIL PRESSURE
CONNECTION SENSOR ALARM
UBERTEMPERATUR
FEHLSTAR
ENGINE OVERHEATED
FAILURE TO START
STATUS
TANK
FUEL
PUMPE ABGESCHALTET
PUMP SWITCHED OFF
KRAFTSTOFFMANGEL
KRAFTSTOFFHAHN GESCHLOSSEN
BETRIEB PUMPE
FUEL DEFICIENCY
VALVE CLOSED
PUMP RUNNING
NETZSPANNUNG
POWER SUPPLY
8.2
5
shows the design of the status display.
Speed or calibration prompt or battery
set and number of start attempts (to the
>
left) and the cause for starting (to the
right).
Engine temperature (°C) and oil
>
pressure (bar)
> Operating hours (H) and fuel level (%)
Voltage of battery A and B or warning
>
indication in case of faults
Settings, and
8.3.2 Fault