Installation
6.5.1
Terminal diagram
1
Main fuse
2
Fuse for motorized ball valve
3
CD degassing control valve
4
Group message
5
Optional for conductivity
6
Ball control valve
(correcting variable (25) / Return value (46))
7
RS-485 interface
8
---
Terminal
Signal
number
1
PE
230 V power supply via mains
2
N
cable and plug.
3
L
4
PE
5N
N
"PU" pump
6 M1
M 1
7
Y2
8
N
CD degassing control valve
9
PE
10
Y 1
11
N
WV make-up valve
12
PE
13
COM
14
NC
Group message (floating).
15
NO
16
Not assigned
External make-up demand
17
Make-up (230
from a pressurisation station;
V)
controller must be set to
18
Make-up (230
"Levelcontrol"!
V)
19
PE shield
Level analogue input, not used
by the device.
20
- Level (signal)
34 — English
Function
Wiring
Pre-wired
Pre-wired
Pre-wired
Pre-wired
User,
optional
User,
optional
---
Vacuum spray degassing — 01.04.2022-Rev. D
9
Digital inputs:
Water meter; Insufficient water
10
Ball control valve (supply)
11
Pressure analogue input
12
External make-up demand (Levelcontrol only)
13
WV make-up valve
14
Pump
15
Mains supply
Terminal
Signal
number
+ Level (+
21
18 V)
22
PE (shield)
23
- Pressure
(signal)
Pressure analogue input
24
+ Pressure (+
18 V)
0 – 10 V
25
(correcting
variable)
0 – 10 V
26
Ball control valve
(feedback)
27
GND
28
+ 24 V (supply)
29
A +
30
B -
RS-485 interface.
31
GND
+ 24 V
Insufficient water switch - dry-
32
running protection
Contact water meter, for
evaluation of the make-up,
33
E1
terminal 32/33 closed = meter
pulse.
Function
Wiring
Pre-wired
Pre-wired
User,
optional
Pre-wired
User,
optional

Werbung