Projektierung Gerät
5
UL-gerechte Installation
5.16
UL-gerechte Installation
5.16.1
Field wiring power terminals
Connection
Line connection
Motor and bra-
king resistor
terminal
PE connection
Terminal screw
for TN/IT sys-
tems
Fastening of
cards
5.16.2
Short circuit current rating
5.16.3
Branch circuit protection
160
Produkthandbuch – MOVIDRIVE
HINWEIS
Folgendes Kapitel wird unabhängig von der Sprache dieser Dokumentation aufgrund
von UL-Anforderungen immer in englischer Sprache und teilweise in französischer
Sprache abgedruckt.
VORSICHT
- Use only tested units with a limited output voltage (V
put current (I
= 8 A) as an external DC 24 V voltage source.
max
- UL certification does not apply to operation in voltage supply systems with a non-
grounded star point (IT systems).
Use 60/75 °C copper wire only.
Tighten terminals to in-lbs (Nm) as follows:
1
2
X1
4.4 – 5.3
X2
M4: 10.6 – 13.3
10.6 – 13.3
M6: 22.1 – 26.6
EMC
Suitable for use on a circuit capable of delivering not more than
5000/10 000 rms symmetrical amperes when protected by circuit breakers and ty-
pe E combination motor controllers as described in the tables below.
65 000 rms symmetrical amperes when protected by fuses, circuit breakers and ty-
pe E combination motor controllers as described in the tables below.
Max. voltage is limited to 240 V (230 V units only) or 500 V (400 V units only).
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes (US) or Canadian Electrical Code, Part 1 (CA).
®
system
Tightening torque in-lbs (Nm)
Frame size
3
4
15.0 –
 15.9
22.1 –
oder
 26.6
8.9 – 10.6
5.3 – 7.1
= DC 30 V) and limited out-
max
5
6
7
75.2  –
88.5 –
123.9 –
 84.1
 132.8
8
 177.0