09.02
4.2.5

Simple application examples for connecting process data with connection assignment

Connecting-up: Refer to Section 3.3 "Control terminal strip"
Factory setting:
Switch-on/off via the PMU, messages and actual values via the terminal strip.
Terminal strip only operational if binary input 5 (BE5) is energized (high signal level corresponds to "reserve").
CUR
-X104/19 BA2
-X104/20 BA2
-X101/6
-X101/9
-X101/10 BE2
-X101/11 BE3
-X101/12 BE4
-X101/13 BE5
-X102/15 AAM
-X102/14 AA
Manual/automatic operation:
Automatic operation (BE5 high signal level): Command input from the automation unit via serial interface
Manual operation (BE5 low signal level):
CUR
-X104/19 BA2
-X104/20 BA2
-X101/6
-X101/9
-X101/10 BE2
-X101/11 BE3
-X101/12 BE4
-X101/13 BE5
-X102/15 AAM
-X102/14 AA
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
Floating contact
Fault
P24
ON/OFF1
BE1
OFF2 (pulse inhibit)
Acknowledge
Basic/reserve
(activates above commands)
Actual Ud value
SST1
Floating contact
Operation
P24
ON/OFF1
BE1
Acknowledge
Fault external 1
Basic/reserve
Actual Ud value
P603.1 = 1002
P554.2 = 1001
P555.2 = 1002
P565.2 = 1003
P590
= 1005
P655.1 = 37
(SST1), the monitoring of external faults via a terminal strip also
possible.
Command input via the terminal strip.
P602.1 = 1002
P554.1 = 1001
P565.1 = 1003
P575.1 = 1004 P575.2 = 1004 (always activ)
P590
= 1005
P655 = 37
PMU
ON/OFF1
P554.1 = 1010
SST
Automation unit
ON/OFF1
P554.2 = 2001
Acknowledge
P565.2 = 2001
ENGLISH
Start-Up
4-9