PNU
OP1S parameter name
Description
*
: Conf.
Par.
P590
Src Base/Reserve
Source of the 'Base / reserve settings' switching command (control word 2,
*
bit 30)
0:
Base setting
1:
Reserve setting
1005: Binary input 5 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
No base/reserve changeover possible
PNU=24EHex; Type=L2; Scaling: 1Hex
P591
Src ContactorMsg
Source of the 'Main contactor energized' message(control word 2, bit 31)
*
0:
1:
1001 to 1005: CUR terminals
4101 to 4116: SCB-SCI1- terminals (serial I/O)
4201 to 4216: SCB-SCI2- terminals (serial I/O)
For details see Section 4.3.1.1
Notes:
If the function is active, pulses are released as soon as the message is
available.
No base / reserve settings possible
PNU=24FHex; Type=L2; Scaling: 1Hex
r599
CW/SW 12-Pulse
Display of control/status word for 12-pulse mode, bit 0 to 15, see Section
3.8.4.
15
13
14
12
7
5
6
4
PNU=257Hex; Type=V2; Scaling: 1Hex
P600
Trg Bit Ready On
Destination of the status bit 'ready for turn ON' (status word 1, bit 0)
*
Power is ON, the drive may be turned on.
Depending on the selected index all settings according to Section 4.3.1.2
(process data wiring of the status word) may be selected.
i01:
GG:
i02:
SCI :
PNU=258Hex; Type=L2; Scaling: 1Hex
P601
Trg Bit Rdy Oper
Destination of the status bit 'Ready for operation' (status word 1, bit 1)
*
All the settings specified in Section 4.3.1.2 (process data wiring of the status
word) are permissible, depending on the index selected
Parameter values, indices: as P600
PNU=259Hex; Type=L2; Scaling: 1Hex
P602
Trg Bit Operat
Destination of the status bit 'Run' (status word 1, bit 2)
*
The unit is in operation.
Parameter values, indices: as P600
PNU=25AHex; Type=L2; Scaling: 1Hex
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
wiring of the control word)
∧ 1
=
Not allowed
No main contactor checkback signal
∧ 1
=
11
9
10
8
3
1
2
0
∧ 1
=
selection of a base drive terminal
selection of a SCI1/2 terminal
∧ 1
=
∧ 1
=
∧ 1
=
Value range
Display
[phys. unit]
Indices
Selection text
Factory-
setting
0 to 6005
-
1005
1 to 4216
-
1
-
0 to 4212
2
0
0 to 4212
2
0
0 to 4212
2
0
ENGLISH
Parameter List
See
Modify
(access /
status)
3/
BR
3/
BR
3/
BR
3/
BR
2/
BR
3/
BR
3/
BR
3/
BR
3/
BR
2/
BR
2/
BR
5-23