09.02
Value
r731.002
r731.003
r731.004
r731.005
r731.006
r731.007
r731.008
r731.009
r731.010
r731.011
r731.012
r731.013
r731.014
r731.015
r731.016
0
9
11
12
r731.017
r731.018
r731.026
r731.027
r731.028
r731.029
Fault and alarm messages:
Detailed information about fault messages can be found in Section 7.
Fault F080
An error occurred during initialization of the CBC board, e.g. incorrect setting of a CB parameter,
incorrect bus address or defective board.
Fault F081
The heartbeat counter (counter on CBC) which is monitored by SIMOVERT for "signs of life" from the
board has not changed for at least 800 ms.
Fault F082
Failure of PZD telegrams or a fault in the transmission channel.
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
Number of correctly received PZD CAN telegrams since Power ON
Number of PZD telegrams lost since Power ON
Telegrams will be lost if the CAN Bus master sends PZD telegrams faster than they can be
processed by the slave.
Counter of Bus Off states since Power ON (alarm A084)
Counter of Error Warning states since Power ON (alarm A083)
Status of the CAN controller
Number of errors occurring during reception of PCD frames
Type of error occurring during reception of PCD frames
Value of error occurring during reception of PCD frames
Number of correctly transmitted PZD CAN telegrams since Power ON
Number of errors during transmission of PZD telegrams
PZD telegrams cannot be transmitted when the bus is overloaded
Type of error occurring during transmission of PCD frames
Value of error occurring during transmission of PCD frames
Number of correctly processed PKW requests and responses since Power ON
Number of PKW request processing errors, e.g. owing to bus overload or missing responses
from CUD1 (see below for error type)
Type of PKW request processing error:
No error
Error transmitting the PKW response (while waiting for a free channel)
Timeout waiting for the PKW response from the CUD1
Timeout waiting for a free channel (bus overload)
Value of error occurring while processing PKW requests
Number of lost PKW requests
Software version of CBC
(e.g. "12" = version 1.2, see also r720)
Software identifier
(extended software version identifier, see also r722)
Date of generation of CBC software
Day (H byte) and month (L byte)
Date of generation of CBC software
Year