Herunterladen Inhalt Inhalt Diese Seite drucken

Analog Input/Output - Siemens SIMOVERT Master Drives 6SE70 Betriebsanleitung

Einspeise-einheit bauform h und k
Vorschau ausblenden Andere Handbücher für SIMOVERT Master Drives 6SE70:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

09.02
PNU
OP1S parameter name
Description
*
: Conf.
Par.
5.11

Analog input/output

P655
CUR AnaOutActVal
Number of the parameters whose value is to be output at the analog output
of the CUR, (terminal X102-14).
PNU=28FHex; Type=O2; Scaling: 1Hex
P656
CUR AnaOut Gain
Gain for the analog output of the CUR (terminal X102-14)
P656 = desired analog output voltage at PWE=100%, if offset=0
The output voltage is calculated with the following formula:
U(out)= [(PWE/100%)
PNU=290Hex; Type=I2; Scaling: 1Hex
P657
CUR AnaOutOffset
Offset for the analog output on the CUR (terminal X102-14)
The analog output can represent voltages of -10V to +10V.
PNU=291Hex; Type=I2; Scaling: 1Hex
P658
AnaOut Conf Curr
Configuration of terminal X102-16 (actual current display)
*
0
Output with correct sign
(positive voltage: motoring current)
(negative voltage: regenerative current)
1
Output absolute value (positive voltage only)
2
Signed output, inverted
(positive voltage: regenerative current)
(negative voltage: motoring current)
3
Output of absolute value, inverted (negative voltage only)
PNU=292Hex; Type=O2; Scaling: 1Hex
P660
SCI AnalogInConf
Configuration of the SCI analog inputs; defines the kind of the input signals
Parameter values
0:
1:
2:
Notes:
Only one signal can be wired per input; alternatively voltage or current
signals can be evaluated.
Voltage and current signals must be connected to different terminals.
Settings 1 and 2 only allow unipolar signals, i. e. the internal process data
are also unipolar.
At setting 2 an input current < 2 mA causes a fault trip (broken wire proof)
The offset scaling of the analog inputs is done via P662.
i001: Sl11
i002: Sl12
i003: Sl13
i004: Sl21
i005: Sl22
i006: Sl23
Condition:
The related SCB board must be reported via P090 and P091, respectively
PNU=294Hex; Type=O2; Scaling: 1Hex
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
∧ 1
=
P656] + P657
*
∧ 0.01 V
=
∧ 0.01 V
=
∧ 1
=
Terminals
X428/3, 6, 9
X428/5, 8, 11
-10 V ... + 10 V
- 20 mA ... + 20 mA
0 V ... + 10 V
0 mA ... + 20 mA
4 mA ... + 20 mA
Slave 1, analog input 1
Slave 1, analog input 2
Slave 1, analog input 3
Slave 2, analog input 1
Slave 2, analog input 2
Slave 2, analog input 3
∧ 1
=
Value range
[phys. unit]
Selection text
0 to 999
±320,00
[V]
-100.00 to 100.00
[V]
0 to 3
signed
absoluteVal
inverted
inv. absVal
0 to 2
Terminals
Parameter List
Display
Indices
Factory-
setting
-
37
-
10.00
-
0.00
-
0
6
0
ENGLISH
See
Modify
(access /
status)
2/
BR
2/
BR
2/
BR
2/
BR
2/
BR
2/
BR
2/
BR
2/
BR
3/
BR
3/
BR
5-27

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis