09.02
•
Configuring examples:
Example 1 : Available:
Required:
♦ Connect-up parameter R037 at the analog output:
P655 "CUR-AA actual values" = 037
♦ Converter the required output range in [%]:
r037 should be taken from the parameter list, Section 5:
Analog output: 100% = 1.35 x P071 (in this case: 1.35 x 400 V = 540 V)
Thus, the following is obtained for the range to be represented:
400 V → 74.05% (Parameter value PWE1)
600 V → 111.07% (Parameter value PWE2)
♦ Define gain factor P656 and offset P657 :
The following is obtained from the formula shown above:
[ ]
Gain
factor
V
[ ]
Offset
V
To be adjusted:
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
P071 (line voltage) = 400 V
Map the actual DC link voltage r037 between 400 and 600 V to 0.00V to
+10.00 V at the analog output
[ ]
[ ]
(
)
−
×
U
V
U
V
100
off1
off2
=
[ ]
[ ]
−
PWE
%
PWE
1
2
−
×
10,00
V
100
=
−
37
%
⎛
[ ]
Gain
factor
−
⎜
=
U
V
off1
⎝
100
⎛
×
27.03
V
74.05
=
−
⎜
0
V
⎝
100
%
gain:
offset:
to be represented as U off1 = 0.00 V
to be represented as U off2 = +10.00 V
−
%
(0.00
V
10.00
=
−
%
74.05
%
111.07
=
27.03
V
[ ]
[ ]
×
⎞
V
PWE
%
1
=
−
⎟
0V
⎠
%
⎞
%
=
−
⎟
19
.
98
V
⎠
P656 = +27,03V
P657 = − 19,98V
×
V)
100
%
%
⎛
×
⎞
27.03
V
74.05
%
⎜
⎟
⎝
⎠
100
%
ENGLISH
Start-Up
4-31