09.02
4.3.9.5
Drive setting
This function is used to change the drive setting(rectifier data, system data).
This includes all parameters that can be written in the "Drive setting" status ("A" ,see right-hand column of the
parameter list in Chapter 5).
Once you have completed the drive setting procedure, you can decide whether to implement the function
selection "Forming" (P052=20) or "Circuit identification" (P052 = 21) or whether just to reset the status
(P052 = 0).
"Drive setting" can be selected in the following statuses: "Switch-on inhibit", "Ready-to-switch-on" or "Fault".
Procedure:
P052 = 5
P051 = 3
if necessary
The "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) operating display appears after the
selected function or selection has been completed
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
(P052 = 5)
Function selection
Access stage Expert mode - (if all parameters, which can be accessed in the
"drive setting" status (A) are required)
All parameters, which can be written into the "drive setting" (A) status (see
right-hand column of the parameter list in Chapter 5), can be changed.
P052 = 20
P052 = 21
P052 = 0
The display appears (r000) while parameters and internal variables are being
de-assigned, depending on the function selected.
Drive setting
Function selection " Forming "
(refer to Section 4.3.9.6)
Function selection " Circuit identification "
(refer to Section 4.3.9.7)
Return
ENGLISH
Start-Up
4-39