06.01
7.2

Alarm messages

The warning message appears periodically as A=Alarm/Warning and a three-digit in the display of the PMU A
warning cannot be acknowledged. It extinguishes automatically when the cause of the warning is eliminated.
Several messages may occur at the same time, in which case they appear one after the other in the display.
If the common rectifier is operated with the OP1S operator panel, the warning appears in the bottom line of the
display. The red LED starts blinking first (see the operating instructions for the OP1S)
Alarm
Parameter
Description
No.
No.
⎯⎯
Bit No.
A015
P953
ext.Warn 1
⎯⎯
Parameter-programmable external warning input 1
has been activated
14
A016
P953
ext. Warn 2
⎯⎯
Parameter-programmable external warning input 1
has been activated
15
A022
P954
LT-Temp.
⎯⎯
The heat sink temperature is > 90 °C
5
or with water-cooled units:
The heat sink temperature is > 118 °C
2
A025
I
P954
⎯⎯
The I
warning is triggered when 90% of the permissible
8
I
2
parameter P785. The permissible I
reached at the maximum permissible load cycle
(see Section 14, Figure 14.1)
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
t Warning
2
t value of the power section is too high. The
t value is reached. See also under fault F022 and
Countermeasures
External warning arrived! Check whether the line to the
relevant binary input is interrupted.
Check parameter P588 Src No Ext Warn 1 .
See also Section 4.3.2.
External warning arrived! Check whether the line to the
relevant binary input is interrupted.
Check parameter P589 Src No Ext Warn 2 .
See also Section 4.3.2.
Measure inlet air and/or ambient temperature. If ϑ >
40°C, note the reduction curves. See Section 14.1.
Check
- whether fan -E1(-E2) is connected and rotating in the
right direction.
- whether the air inlet and outlet openings are clean and
clear.
- the connection of the temperature sensor to -X30
(-X31, -X32).
With water-cooled units:
-
Water inlet temperature too high, cooling circuit
interrupted or cooling water pump faulty
Check whether the rated DC current of the
rectifier/regenerating unit is adequate for the specific
application.
2
t value is
Fault and Alarm Messages
ENGLISH
7-9