09.02
4.2.3
Parameterization for "Expert application"
Parameterization can be simplified by selecting an appropriate factory setting via parameter P077 using special
functions such as 12-pulse mode with two commom rectifiers coupled via a peer-to-peer link. In this case, this is
carried out by selecting the function "Generate factory setting" as described in Section 4.3.9.1 with P077≠0.
Then the parameterization shown in the following diagram can be carried out.
In all other cases, the following parameterization is started immediately.
P050 =
P051 = 3
P053 =
yes
Commands
via OP1S?
no
P554 = 2001
P555 = 2001
P052 = 5
P071 =
P076 =
P160 =
Idle time
yes
of converter
>1year
no
P408 =
P052 = 20
P key
Switch-on
Forming
r000 ≤
o
Wait to
Ud<50V
Siemens AG
6SE7087-6AK85-0AA0
Common Rectifier
Operating Instructions
Language (only important when an OP1S is in use; see Section 9.4):
0: German, 1: English, 2: Spanish, 3: French, 4: Italian
Access stage "Expert mode"
Parameterization enable
e.g. with P053=6, the parameters from the parameterization unit (PMU)
and from serial interface 1 of the basic unit (SST1- and therefore also from
the optional user-friendly operator panel OP1S) can be modified
Operator control
In order to avoid having to wait until the link circuit voltage drops below
20% before switching off, set the parameter P554 = P555.
If the unit is to be switched on and off via the optional user-friendly
operator panel OP1S:
P554=2001 Source for control command "ON/OFF1"
P555=2001 Source for control command "OFF2"
Drive setting
Supply voltage [V]
Value of the rated voltage at the rectifier bridge
Value of the rated voltage at the rectifier bridge
P076 = 00x No power section connected in parallel
(also see Section 3.7 and Section 5, P076)
Current limits:
P160 = Max. supply current (in % P075 rated current of common
Forming the DC link (if necessary; see Section 4.3.9.6)
- The common rectifier must be in status o 009 or less
(give SWITCH OFF command!).
- Set P408 (forming time: 1.0 to 600.0 minutes).
- Select function (P052 = 20)
- Press the P key on the PMU
- Switch on: Press the I key on the PMU
- Forming of the DC link takes place
009
- Following the forming process, the status display is activated.
(see r006)
01x 1 common rectifier parallel unit connected in parallel with
the basic unit
02x 2 common rectifier parallel units connected in parallel with
the basic unit
rectifier (factory setting: +150% only briefly available)
ENGLISH
Start-Up
4-7