Code
Description
Error, serial
„E39"
communication error on
sync bus
Error, limit switch
„E41"
configuration (incorrect
drive)
Difference between
„E42"
master and slave too
great
„E45"
Internal error
A faulty entry has been
„E51"
detected in the memory
„E52"
Internal error
Drive 3 motor current
„E71"
too high
Drive 4 motor current
„E72"
too high
Blockage detected on
„E73"
drive 3
Blockage detected on
„E74"
drive 4
Lag error between
„E75"
controller 3 and drive 3
Lag error between
controller 4
„E76"
and drive 4
Difference between
„E77"
drive 1 and drive 3 too
great
Difference between
„E78"
drive 1 and drive 4 too
great
284
Troubleshooting
Check the connections in the synchro system and of the
individually connected controls.
The connected drive is not suitable for the configuration of
◼ Use a suitable drive for configuration of the control
the control.
◼ Check the drive for a possible defect
The drive may be faulty.
Check the load on the drives.
Contact RK Rose+Krieger GmbH.
The control is automatically reset to the factory settings. Carry
out an initialization run.
Contact RK Rose+Krieger GmbH.
The control detects that a drive is drawing too much current.
◼ Mechanical overload of the system
If the error occurs frequently, check for the following:
◼ Possible drive defects
The control has detected an abruptly occurring excessive
current at the drive, which indicates a mechanical blockage.
Check the system for mechanical blockages and remove them
as necessary.
The drive does not move at the specified speed and/or may
◼ Check the drive for excessive load
be faulty.
◼ Make sure the correct drives are set in the control
If the error message is still displayed, the control or a drive
could be faulty. Contact RK Rose+Krieger GmbH.
◼ Check the system for mechanical load
◼ Carrying out initialization run
If the error message is still displayed, the control or a drive
'E78' could be faulty. Contact RK Rose+Krieger GmbH.
Control RK MultiControl II duo/RK MultiControl II quadro