9.7

Messages after replacement of DRIVE-CLiQ components

After DRIVE-CLiQ components are replaced (TM15, TM31, SMC30) by spare parts, no
message is generally output after switching on, as an identical component is identified and
accepted as a replacement part when the system boots.
If, however, a fault message of the "topology fault" category is displayed, contrary to
expectations, one of the following faults may have occurred when replacing a component:
● The connections have been swapped when connecting the DRIVE-CLiQ cables.
● The level for the topology comparison has been set too high.
Automatic firmware update
A firmware update for the replaced DRIVE-CLiQ component may run automatically after
switching on the electronics.
● The following LEDs will flash slowly to indicate that an automatic firmware update is in
progress: the "RDY" LED on the control unit (orange, 0.5 Hz) and an LED on the relevant
DRIVE-CLiQ component (green/red, 0.5 Hz).
● Once the automatic firmware update is complete, the "RDY" LED on the control unit will
flash quickly (orange, 2 Hz), as will an LED on the relevant DRIVE-CLiQ component
(green/red, 2 Hz).
● To complete the automatic firmware update process, a POWER ON is required (switch
the device off and back on again).
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
NOTICE
The SINAMICS DCM Cabinet must not be shut down during this process.
9.7 Messages after replacement of DRIVE-CLiQ components
Maintenance and servicing