Installation / Preparation for start-up

4.6 Setting the Node-ID and Baud rate by means of LSS services

4.6.1 Configuration of the Node-ID, sequence

Assumption:
-
-
-
-
Procedure:

4.6.2 Configuration of the Baud rate, sequence

Assumption:
-
-
-
-
Procedure:
 TR-Electronic GmbH 2010, All Rights Reserved
Page 144 of 183
LMT or LSS services enabled by means of the switches
LSS address unknown
only one LSS slave should be in the network
the Node-ID 12 dec. shall be adjusted
Perform service 04 Switch state global protocol,
Mode = 1, to switch the LSS slave into Configuration state.
Perform service 17 Configure Node-ID protocol, Node-ID = 12.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
Perform service 23 Store configuration protocol.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
--> LSS slave is reset and is in condition PRE-OPERATIONAL.
LMT or LSS services enabled by means of the switches
LSS address unknown
only one LSS slave should be in the network
the Baud rate 125 kbit/s shall be adjusted
Perform service 04 Switch state global protocol,
Mode = 1, to switch the LSS slave into Configuration state.
Perform service 19 Configure bit timing parameters protocol,
Table Selector = 0, Table Index = 4
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
Perform service 23 Store configuration protocol.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
--> LSS slave is reset and is in condition PRE-OPERATIONAL.