12.2 Number format of 32-bit values

The weight values are generally displayed with no comma; the number of
decimal places matches the calibration (see also weight display on top display
line).
32-bit value no.
Word no.
The value range for Int32 (32-bit integer) is -2147483648 to 2147483647.
The value range for UInt32 (32-bit unsigned integer) is 0 to 4,294,967,295.

12.3 Input and output words

The content of the data words is determined by the default settings. A
distinction is made between "Standard" and "Filler".
The following tables provide an overview of the content of the existing data
words.
12.3.1 Input words WTX120-> PLC ("Standard" application)
Word Name
0
Net measured value
2
Gross measured value
4
Weight status (see chap­
ter 12.4.2)
WTX120
n
N (high word)
A04500_02_Y00_00 HBM: public
N+1 (low word)
Type
Bit
Contents
S32
S32
Bit
.0
General scale error
Bits
.2-3
Display status
Bit
.4
Scale in motion
Bit
.5
Calibration switch open
Bit
.6
Manual tare
Bit
.7
Net
Bits
.8-9
Measurement range
Bit
.11
True zero
Bit
.12
Within zero range
PLC link