Supervisor mode
Information
The residual flow status bit is already set during dosing delay time 1, see also
16.2.32 Residuals.

9.2.34 Residual flow time

The residual flow time starts after the fine flow cut-off point is reached. It
records the residual flow. At the end of this delay time, checkweighing is
carried out.
Recording the residual flow is important for correct measurement of the actual
weight in checkweighing, and therefore also for the optimization, where
appropriate. The time to set depends on the dosing device and the settling time
of the digital filter.

9.2.35 Stabilization time

The stabilization time follows the fill flow phase and residual flow phase.
If standstill recognition (MTD) is active, checkweighing is carried out after
standstill, but within the stabilization time. Otherwise checkweighing is started
immediately.
If no standstill occurs within the stabilization time, the actual weight is always
measured once the stabilization time expires.

9.2.36 Emptying time

By setting parameter P1 > 0 you activate the emptying time. Emptying starts
immediately after checkweighing. Then the preconfigured control output
(Empty) is activated to carry out emptying, and is automatically switched to the
gross measurement value. Emptying is regarded as complete when the gross
weight in emptying mode is below the empty weight or when the emptying
time (in both emptying modes) is exceeded. If the emptying time is exceeded,
emptying ends, regardless of whether the scale is empty or not. When
emptying is complete, the end of the filling process is indicated by the Finished
signal (also see chapter 9.2.15 "Empty weight").
WTX120
115
A04500_02_Y00_00 HBM: public