Supervisor mode
Information
This setting is ignored in a downwards weighing.

9.2.17 Coarse flow cut-off point

The coarse flow cut-off point must not be higher than the fine flow cut-off point.
After the target weight is entered, the coarse flow cut-off point is automatically set
to 50% of the target weight if no coarse flow cut-off point is set. If optimization is
activated (parameter P1 > 0), the coarse flow cut-off point is tracked automatically.
The coarse flow cut-off point must not be higher than the fine flow cut-off point.
The minimum fine flow may define a minimum distance to the fine flow cut-off
point:

9.2.18 Coarse flow monitoring

This option is used for breakage monitoring during the coarse flow phase (sack
breakage). Enter the increase in weight you expect per time interval (Coarse
monitor) during a normal filling process. At the end of the coarse flow lockout
time, the increase is checked after each time interval (Coarse monitor). If the
weight increase rate is not exceeded, the fact is interpreted as a breakage of
the container being filled, and dosing is aborted. The coarse flow monitor is
only active during the coarse flow phase.

9.2.19 Fine low cut-off point

Sets or reads the fine flow cut-off point. If you specify a target weight, the fine
flow cut-off point is automatically set to 95% of the target weight if no fine flow
cut-off point is set.
106
Coarse flow cut-off point
Fine flow cut-off point – minimum fine flow