9.2.28 Coarse flow monitoring (time interval)

This command is used for breakage monitoring during the coarse flow phase
(sack breakage). Enter the increase in weight you expect per time interval
during a normal filling process. At the end of the coarse flow lockout time, the
increase is then checked after each time interval. If the weight increase rate
is not exceeded this fact is interpreted as a breakage of the container being
filled, and dosing is aborted. Coarse flow fill flow monitoring is deactivated
when the coarse flow cut-off point is reached.
When a break is detected:
S Coarse flow and fine flow are deactivated.
S If Bit 6 (Alarm) is set to 1 in dosing status (SDO),
S then if Alarm: Fill flow On is set, the alarm is triggered,
S dosing control switches to the stop status.