Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIMATIC FM 357 Handbuch Seite 131

Mehrachsbaugruppe für servo- bzw. schrittantrieb
Inhaltsverzeichnis

Werbung

Programmieren der FM 357
Aufrufbeispiel
Das vorliegende Beispiel enthält die relevanten Standardeintragung für den OB 82
und den Aufruf der Grundfunktion im FC 5.
AWL
VAR_TEMP
OB82_EV_CLASS
OB82_FLT_ID
OB82_PRIORITY
OB82_OB_NUMBR
OB82_RESERVED_1
OB82_IO_FLAG
OB82_MDL_ADDR
OB82_MDL_DEFECT
OB82_INT_FAULT
OB82_EXT_FAULT
OB82_PNT_INFO
OB82_EXT_VOLTAGE
OB82_FLD_CONNCTR
OB82_NO_CONFIG
OB82_CONFIG_ERR
OB82_MDL_TYPE
OB82_SUB_NDL_ERR
OB82_COMM_FAULT
OB82_MDL_STOP
OB82_WTCH_DOG_FLT
OB82_INT_PS_FLT
OB82_PRIM_BATT_FLT :BOOL;
OB82_BCKUP_BATT_FLT :BOOL;
OB82_RESERVED_2
OB82_RACK_FLT
OB82_PROC_FLT
OB82_EPROM_FLT
OB82_RAM_FLT
OB82_ADU_FLT
OB82_FUSE_FLT
OB82_HW_INTR_FLT
OB82_RESERVED_3
OB82_DATE_TIME
END_VAR
BEGIN
CALL FC 5;
// HIER DIAGNOSEANWENDERPRO-
1)
// GRAMM
END_ORGANIZATION_BLOCK
1) Werden an die CPU, außer FM 357, noch andere diagnoseauslösende Baugruppen an-
geschlossen, so können Sie hier das Reaktionsprogramm einfügen.
6-32
:BYTE;
:BYTE;
:BYTE;
:BYTE;
:BYTE;
:BYTE;
:INT;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BYTE;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:BOOL;
:DATE_AND_TIME;
EINFUEGEN
//16#39, Event class 3, Entering
//event state, Internal fault event
//16#XX, Fault identification code
//26/28 (Priority of 1 is lowest)
//82 (Organization block 82, OB82)
//Reserved for system
//Input (01010100), Output
//(01010101)
//Base address of module with fault
//Module defective
//Internal fault
//External fault
//Point information
//External voltage low
//Field wiring connector missing
//Module has no configuration data
//Module has configuration error
//Type of module
//Sub-Module is missing or has error
//Communication fault
//Module is stopped
//Watch dog timer stopped module
//Internal power supply fault
//Primary battery is faulty
//Backup battery is faulty
//Reserved for system
//Rack fault, only for bus interface
//module
//Processor fault
//EPROM fault
//RAM fault
//ADC fault
//Fuse fault
//Hardware interrupt input faulty
//Reserved for system
//Date and time OB82 started
Mehrachsbaugruppe FM 357 für Servo- bzw. Schrittantrieb