Value
Description
0
Auto
1
Manual
2
Set
The 'Bank Settings Lock' parameter is defined as follows:
Value
Description
0
Unlocked
1
Locked
5.5.3.3. Protection (alarm relay n°1) (GroupID = 0x0803)
Byte
Description
Offset
0
V min prot.
4
V max prot.
8
T1 max prot.
12
T2 max prot.
16
T3 max prot.
20
T4 max prot.
24
T5 max prot.
28
T6 max prot.
32
T7 max prot.
36
T8 max prot.
40
THDV max
prot.
44
Irms max
prot.
48
Ext. prot.
49
V min Enable
50
V max Enable
51
T1 max Ena-
ble.
52
T2 max Ena-
ble.
STATUS
Approved
Units
RVT RVT3P Data
V
*
*
V
*
*
°C or
*
*
°F
°C or
*
*
°F
°C or
*
*
°F
°C or
*
*
°F
°C or
*
*
°F
°C or
*
*
°F
°C or
*
*
°F
°C or
*
*
°F
%
*
*
Ä
*
*
*
*
*
*
*
*
*
*
*
*
SECURITY LEVEL
Public
Size in
Default
type
bytes
value
Float
4
90
Float
4
480
Float
4
40
Float
4
40
Float
4
40
Float
4
40
Float
4
40
Float
4
40
Float
4
40
Float
4
40
Float
4
10
Float
4
1
Byte
1
0
Byte
1
0
Byte
1
0
Byte
1
0
Byte
1
0
DOCUMENT ID
9AKK106713A9758
RVT CO MM UNI CATI O N
Min
Max
Modb
value
value
@
5
9e6
43001
5
9e6
43003
-40
150
43005
-40
150
43007
-40
150
43009
-40
150
43011
-40
150
43013
-40
150
43015
-40
150
43017
-40
150
43019
0.5
1000
43021
0.1
9e6
43023
0
1
43025
0
1
43026
0
1
43027
0
1
43028
0
1
43029
REV.
LANG.
PAGE
K
en
42/71
© 2022 Hitachi Energy. All rights reserved.