Herunterladen Diese Seite drucken

Parameter Changes And Access - Hitachi Abb Rvt Installation Und Betriebsanleitung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 161
Configuration
Universal
Access protected
Application Specific
Measurement
Application Specific
Info
Universal
Application Specific
The access type is given from the perspective of the local or distant user interface.
The "Configuration – Universal" parameters are considered as system parameters. As such, they are only modifiable
by users that have at least "Administrator" rights.
The "Configuration – Access Protected" parameters can be modified by users that have at least "Configurator" rights
so that their value can be reset or modified.
The "Configuration – Application Specific" parameters can be modified by users that have at least "Configurator"
rights.
The other read-only parameters are accessible by any kind of user.
Values of single parameters within a group can be of different types. Here is a list of these types and the associated
memory usage:
Type
Size in bytes
Byte
1
Signed char
1
Word
2
Dword
4
64-bits
8
Time
6
Float
4
String
Variable
5.3.

Parameter Changes and access

Please note that the RVT is fitted with some locking function, independently than the administrator rights.
– MODE: the RVT must be in SET Mode to allow parameters settings modifications.
– LOCK SWITCH: the lock switch have to be released
– BANK SETTINGS: the parameter Bank Settings must be set to Unlocked.
– The parameter COMMUNICATION LOCK is used to add an access level to users. When locked, all parameter set-
tings modifications (except the Communication lock item setting) from the RVT touchscreen are forbidden. Param-
eters may meanwhile be modified by the communication access only (provided all others access levels are ful-
filled).
Variable
Mode
STATUS
Approved
R/W
R/W
R/W
R
R
R
Remarks
Unsigned
Signed
Unsigned
Unsigned
Unsigned
Same format as used in the RTC parameter
IEEE-754 floating-point number
NULL-terminated ASCII string
Group ID
locked
0x0802
0 : AUTO
1 : MAN
SECURITY LEVEL
Public
Lower
0x0000
0x0100
0x0800
0x1000
0x2000
0x2100
Unlocked
2 : SET
DOCUMENT ID
9AKK106713A9758
RVT CO MM UNI CATI O N
Upper
0x0FF
0x07FF
0x0FFF
0x1FFF
0x20FF
0x2FFF
REV.
LANG.
PAGE
K
en
23/71
© 2022 Hitachi Energy. All rights reserved.
loading