Device menu
Parameter
Max. pulse frequency 1
Max. pulse frequency 2
Delay 1
Delay 2
Switch-off 1
Switch-off 2
Alarm tolerance
Alarm delay
(
1
) The unit displayed is dependent (by the execution of the plug-in card type of measurement) on the associated analysis slot.
10.5.3

Setpoints

Here, the set point of the controller channel can be changed.
Call: Device menuèParameterisationtarget valuesController target value 1 to 4 ètarget
value 1
Parameters
Target value X
417102269 Rev. 2-08.2020
Selection /
option
Explanation
0 to 240 min-1
For continuous controllers with pulse frequency
output
0 to 999.9 s
Delay the switch-on edge at limit switch
behaviour (proportional band = 0)
0 to 999.9 s
Delaying the switch-on limit switch behaviour
[1](Proportional range = 0)
Maximum amount of deviation without triggering
0 to 999.9 (1)
an alarm, when exceeding this amount, the
controller monitor triggers a "Dosing alarm" from
0 to 9999 s
The delay of dosing alarms allows for a
temporary violation of the alarm tolerance.
Selection /
setting
possibility
Explanation
0.0000 - 99999
Target value adjustment
178
Default
60 min-1
0.0 s
0.0 s
0,0
0.0 s
Default
Ci: 200.00
mS/cm
Cr: 200.00
uS/cm
pH: 7,00
ORP: 300.00
mV
Cl: 10.000 mg/l
Cd: 0.3000 mg/l
Pa: = 1000,0
mg/l