Alarm
Code
01
Min. pressure
Compressor 1 insufficient
02.1
water
02.2
Compressor 2 insufficient
water
03
High water
04.1
Compressor 1
04.2
Compressor 2
05
Compressor run-on time
06
Make-up time
07
Make-up cycles
08
Pressure measurement
09
Level sensor
10
Maximum pressure
11
Make-up volume
15
Make-up valve
16
Power failure
19
Stop > 4 h
20
Max. make-up volume
21
Maintenance recommended Set value exceeded.
24
Softening
30
I/O module fault
31
EEPROM defective
32
Undervoltage
33
Adjustment parameter faulty EEPROM parameter memory defective.
34
Main board communication
faulty
Causes
Set value exceeded.
Water loss in the system.
Compressor fault.
Controller in Manual mode.
Set value not reached.
Make-up disabled.
Air in the system.
Dirt trap clogged.
Set value exceeded.
Make-up disabled.
Water intake through a leak in a thermal transfer
medium of the user.
Vessels too small.
Compressor disabled.
Fuse defective.
Set value exceeded.
Severe water loss in the system.
Air lines leaking.
Solenoid valve in the overflow line does not close.
Set value exceeded.
Water loss in the system.
Make-up line not connected.
Make-up rate insufficient.
Make-up hysteresis too high.
Set value exceeded.
Leakage in the system.
Controller receives incorrect signal.
Controller receives incorrect signal.
Set value exceeded.
Pressure relief pipe not functioning.
Dirt trap clogged.
Only if "With water meter" is activated in the Customer menu.
Set value exceeded.
Severe water loss in the system.
Contact water meter measures without make-up request.
No power.
Device is in Stop mode for more than 4 hours.
Set value exceeded.
Set value for soft water capacity exceeded.
Time interval for replacement of the softening cartridge
exceeded.
I/O module defective
Connection between option card and controller faulty.
Option card defective.
EEPROM defective
Internal calculation error
Supply voltage too low.
Connecting cable defective.
Main board defective.
Reflexomat Touch — 09.2020 - Rev. A
Remedy
Check set value in the Customer or Service menu.
Check water level.
Check compressor.
Set the controller to Automatic mode.
Check set value in the Customer or Service menu.
If necessary, manually add water.
Check functioning of the "PV1" solenoid valve.
Clean the dirt trap.
Check set value in the Customer or Service menu.
Check functioning of the "WV1" solenoid valve.
Drain water from the primary vessel.
Check user's thermal transfer medium for leaks.
Check functioning of "CO" compressor.
Check in manual mode, reduce back
pressure.
Replace the fuse.
Check set value in the Customer or Service menu.
Check the water loss and correct, if necessary.
Seal any leak in the air system.
Check functioning of the "PV1" solenoid valve.
Check set value in the Customer or Service menu.
Check water level.
Connect make-up line.
Increase the make-up volume.
Correct the make-up hysteresis in the service
menu.
Check set value in the Customer or Service menu.
Seal any leak in the system.
Connect the plug.
Check functioning of the pressure sensor.
Check the cable for damage.
Check functioning of the load cell.
Check the cable for damage.
Connect the plug.
Check set value in the Customer or Service menu.
Check functioning of the pressure relief pipe.
Clean the dirt trap.
Check set value in the Customer or Service menu.
Check water loss in the system and repair, if
necessary.
Water volume per contact incorrectly set in the
Service menu.
Check the make-up valve "WV" for leaks.
Connect to power supply.
Set the controller to Automatic mode.
Reset the "Make-up volume" meter in the Customer
menu.
Carry out maintenance.
Replace the softening cartridges.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check power supply.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Controller
Alarm
reset
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"
"OK"