Service Menu; Default Settings - Reflex Servitec 35 Originalbetriebsanleitung

Control touch steuerung
Vorschau ausblenden Andere Handbücher für Servitec 35:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
Controller
PM
Description
code
032
Soft water capacity ... l
Calculation required before input.
Fillsoft I + softening:
Soft water capacity = 6000 l / hardness reduction.
Fillsoft I + desalination:
Soft water capacity = 3000 l / hardness reduction.
Fillsoft II + softening:
Soft water capacity = 12000 l / hardness reduction.
Fillsoft II desalination:
Soft water capacity = 6000 l / hardness reduction.
033
Hardness reduction ... °dH = GHactual – GHtarget
Can be called when softening or desalination is active.
Calculate the required reduction in overall hardness GH
before input.
034
replacement interval... months (for softening cartridges
according to manufacturer).
007
Maintenance interval... months
008
Floating contact
Message selection >
Message selection: only messages marked with "√" are
output.
All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
Information >
Position of the "PV" 2-way motorized ball valve at the pressure
side of the pump.
Position in %
Software version
10.1.1.2 Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1.
Press "Settings".
The controller switches to the setting area.
2.
Press "Customer >".
The controller opens the Customer menu.
40 — English
3.
Press the required area.
4.
Set the system-specific values for the individual areas.
Press "i" to display a help text for the selected area.
Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
10.1.2
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service. A partial summary of the settings stored in the Service menu is
proved in the Chapter Default settings,  10.1.3 "Default settings",  40.
10.1.3
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Language
Time
Date
Servitec
Minimum operating
pressure p0
Safety valve, pressure
Degassing
Degassing programme
Continuous degassing time 24 hours
Make-up
Maximum make-up
quantity
Maximum make-up time
Maximum make-up cycles
Vacuum spray degassing — 18.12.2019-Rev. A
The controller switches to the selected area.
Use the scroll bar to navigate through the list.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".

Service menu

Default settings

Setting
EN
Magcontrol
1.5 bar
3.0 bar
Continuous
degassing
0 Litres
20 minutes
3 cycles within 2
hours
Remarks
Display language
For systems with diaphragm-
type expansion vessel
Only Magcontrol
Actuating pressure of the
system's heat generator safety
valve
Only if controller with "With
water meter yes"
Magcontrol and Levelcontrol
Magcontrol and Levelcontrol

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Servitec 60Servitec 75Servitec 95

Inhaltsverzeichnis