Type And Frequency Of Scheduled Checks; Prolonged Shutdown; End-Of-Day Shutdown; Start-Up After Prolonged Shutdown - RHOSS TCCE 135 Gebrauchsanweisung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 73
I.3.10.2 Secondary control panel alarms
(CC – AP&CC – LA – AP&LA)
In the CC – AP&CC – LA – AP&LA models, on the electric panel there
is a control panel which regulates condensation pressure. In case of
alarm, after resetting the main control panel, it may be necessary to
reset any alarms which may be present on the secondary control panel.
The display of the secondary control panel shows the alarms which may
be present in the unit. A list is shown below of alarms and possible
reset types.
Alarm
Alarm description
E00
Sensor faulty or disconnected
E02
Memory error
E04
High pressure alarm
E05
Low pressure alarm
I.3.11
TYPE AND FREQUENCY OF SCHEDULED
CHECKS
DANGER!
Scheduled maintenance must be carried out by
skilled technicians, qualified to work on
conditioning and cooling products.
To guarantee the unit runs regularly and efficiently, it is necessary to
schedule an overall inspection at regular intervals to prevent
malfunctions which could damage the main machine components (see
SECTION II: INSTALLATION AND MAINTENANCE).
I.3.12

PROLONGED SHUTDOWN

When the appliance is not used for long periods of time, disconnect it
from the power supply by means of the main isolator switch.
IMPORTANT!
If the unit is not used during the winter period, the
water contained in the system may freeze.
All the water contained in the circuit must be emptied before the onset
of winter. During installation, consider mixing the water in the circuit with
the correct proportion of ethylene glycol (antifreeze) to guarantee
protection against freezing (see SECTION II: INSTALLATION AND
MAINTENANCE).
To reset the alarm, press the
PRG/mute key for 5 seconds.
If the alarm is properly reset,
the value of the pressure
measured by the sensor. If the
alarm condition persists, the
alarm indication reappears on
the display.
Reset
Automatic
Automatic
Automatic
Automatic
The "power supply" LED
switches off indicating that the
unit is no longer connected to the
power supply.
I.3.13

END-OF-DAY SHUTDOWN

The unit can be shut down from the control panel or, if present, from the
remote control panel. This ensures the power supply to the plate
exchanger heating element.
I.3.14
START-UP AFTER PROLONGED
SHUTDOWN
Before starting up the unit again:
• check that the air side heat exchanger is in good condition, well
ventilated and clean;
• bleed any air from the water system;
• make sure the required amount of water circulates inside the
exchanger.
33
SECTION I: USER
Press the ON/OFF, RESET-
DOWN key for 2 seconds.
The compressor and active
function mode LEDs go out.
The power supply LED
remains lit, indicating that the
unit is connected to the power
supply.