Malfunctions and troubleshooting
Fault description
Unit is running but is not performing
any metering (electrical problems)
Unit is running with reduced metering
performance (performance problems)
Possible error message on a primary
control unit (metering error alarm)
PLUS
OGM
is not supplying any pulses
even though the pump is running
Empty signal/prewarning even though
the supply container is full
MAN053089 Rev. 1-11.2023
Cause
Power supply cable damaged Replace power supply cable
Mains voltage incorrect
Connection faulty
Solenoid valve fully or
partially closed
Suction line not airtight
Metering point not ready for
use
Metering point back-pressure
too high
Unit does not start up
Solenoid valve closed
Metering point not ready for
operation
Suction tube leaking
Solenoid valve closed on
product side
Pump leaking
Pipe connection leaking
Solenoid valve leaking
Pump output is set lower
than the minimum flow on the
OGM
PLUS
Gas accumulation in the
pump head
Oval gear meter blocked with
dirt
Suction lance in supply
container is incorrectly
positioned
Float in the suction lance
blocked
Plug or stopper on the
suction lance loose or not
inserted
Cable fault on the suction
lance
72
Remedy
Check mains voltage as shown on the rating
plate
Check connection in accordance with the
connection diagram
Open the solenoid valve completely, replace it if
necessary
Check the complete suction tube and replace in
the event of air leaks
Check and repair metering point functions
Check metering point back-pressure using the
metering point specifications
n
Check medium connection and filled lines
n
Check pump
Open the solenoid valve completely, replace it if
necessary
Bring the metering point to operational
readiness or repair as necessary
Check suction tube and seal or replace leaking
part
Open the solenoid valve on the product side,
replace if necessary
See the operating instructions for the pump
(
Ä
'Available instructions' on page 5 ).
Tighten the armatures or replace the seals as
required
Replace the solenoid valve
Increase the pump output or use OGM
a lower start-up limit
n
Bleed the pump
n
Flush pump with flushing medium and
clean or replace valves
Flush oval gear meter with flushing medium and
remove dirt
Correctly position the suction lance in the
supply container
Repair float
n
Check that the plug and stopper are (firmly)
inserted
n
Clean contacts
Change empty signal settings
PLUS
with