The properties of the slot are displayed in the Device view in the inspector
window after selecting Properties -> General.
To set the F-parameters, the PROFIsafe directory must be selected in the
directory tree of the General tab.
The F_Dest_Add entry and the setting of the address switches for the measuring
system must correspond!
The parameter value for the parameter F_iPar_CRC results from the set parameter
data set for the iParameters and the calculated CRC value. See chap.: 4.3.1 "Setting
the iParameters" on page 109.
The blocks for the safety program are generated automatically. The only
precondition is that the F-CPU has activated the fail-safe. (See chap.: 4.2.1
"Defining the properties of the hardware configuration" on page 102).